Toshiba HFC R-410A Air Conditioner User Manual


 
38
Single outdoor unit
Heat pump Cooling only Nominal Voltage Compressor Fan motor Power supply
MMY- MMY- voltage range
(V-ph-Hz) Min. Max. RLA kW FLA MCA MOCP
MAP0501HT8 MAP0501T8 400-3-50 342 457 4.0 + 4.0 0.60 0.8 16.5 20
MAP0601HT8 MAP0601T8 400-3-50 342 457 4.6 + 4.6 0.60 0.8 16.5 20
MAP0801HT8 MAP0801T8 400-3-50 342 457 5.2 + 5.2 0.60 1.0 20.0 30
MAP1001HT8 MAP1001T8 400-3-50 342 457 6.5 + 6.5 0.60 1.1 22.5 30
MAP1201HT8 MAP1201T8 400-3-50 342 457 9.5 + 9.5 0.60 1.1 24.5 30
Combination of outdoor units
Heat pump Cooling only Nominal Voltage Compressor Fan motor Power supply
MMY- MMY- voltage range Unit No. 1 Unit No. 2 Unit No. 3 Unit No. 4
(V-ph-Hz Min. Max. RLA RLA RLA RLA kW FLA MCA MOCP
AP1401HT8 AP1401T8 400-3-50 342 457 5.2 + 5.2 4.6 + 4.6 0.6 × 2 1.0 + 0.8 36.5 40
AP1601HT8 AP1601T8 400-3-50 342 457 5.2 + 5.2 5.2 + 5.2 0.6 × 2 1.0 + 1.0 40.0 50
AP1801HT8 AP1801T8 400-3-50 342 457 6.5 + 6.5 5.2 + 5.2 0.6 × 2 1.0 + 1.1 42.5 50
AP2001HT8 AP2001T8 400-3-50 342 457 6.5 + 6.5 6.5 + 6.5 0.6 × 2 1.1 + 1.1 45.0 60
AP2201HT8 AP2201T8 400-3-50 342 457 5.2 + 5.2 5.2 + 5.2 4.6 + 4.6 0.6 × 3 1.0 + 1.0 + 0.8 56.5 70
AP2211HT8 AP2211T8 400-3-50 342 457 9.5 + 9.5 6.5 + 6.5 0.6 × 2 1.1 + 1.1 47.0 60
AP2401HT8 AP2401T8 400-3-50 342 457 5.2 + 5.2 5.2 + 5.2 5.2 + 5.2 0.6 × 3 1.0 + 1.0 + 1.0 60.0 70
AP2411HT8 AP2411T8 400-3-50 342 457 9.5 + 9.5 9.5 + 9.5 0.6 × 2 1.1 + 1.1 49.0 60
AP2601HT8 AP2601T8 400-3-50 342 457 6.5 + 6.5 5.2 + 5.2 5.2 + 5.2 0.6 × 3 1.1 + 1.1 + 1.0 62.5 70
AP2801HT8 AP2801T8 400-3-50 342 457 6.5 + 6.5 6.5 + 6.5 5.2 + 5.2 0.6 × 3 1.1 + 1.1 + 1.0 65.0 80
AP3001HT8 AP3001T8 400-3-50 342 457 6.5 + 6.5 6.5 + 6.5 6.5 + 6.5 0.6 × 3 1.1 + 1.1 + 1.1 67.5 80
AP3201HT8 AP3201T8 400-3-50 342 457 5.2 + 5.2 5.2 + 5.2 5.2 + 5.2 5.2 + 5.2 0.6 × 4 1.0 + 1.0 + 1.0 + 1.0 80.0 90
AP3211HT8 AP3211T8 400-3-50 342 457 9.5 + 9.5 6.5 + 6.5 6.5 + 6.5 0.6 × 3 1.1 + 1.1 + 1.1 69.5 80
AP3401HT8 AP3401T8 400-3-50 342 457 6.5 + 6.5 5.2 + 5.2 5.2 + 5.2 5.2 + 5.2 0.6 × 4 1.1 + 1.0 + 1.0 + 1.0 82.5 100
AP3411HT8 AP3411T8 400-3-50 342 457 9.5 + 9.5 9.5 + 9.5 6.5 + 6.5 0.6 × 3 1.1 + 1.1 + 1.1 71.5 80
AP3601HT8 AP3601T8 400-3-50 342 457 6.5 + 6.5 6.5 + 6.5 5.2 + 5.2 5.2 + 5.2 0.6 × 4 1.1 + 1.1 + 1.0 + 1.0 85.0 100
AP3611HT8 AP3611T8 400-3-50 342 457 9.5 + 9.5 9.5 + 9.5 9.5 + 9.5 0.6 × 3 1.1 + 1.1 + 1.1 73.5 90
AP3801HT8 AP3801T8 400-3-50 342 457 6.5 + 6.5 6.5 + 9.5 6.5 + 6.5 5.2 + 5.2 0.6 × 4 1.1 + 1.1 + 1.1 + 1.0 87.5 100
AP4001HT8 AP4001T8 400-3-50 342 457 6.5 + 6.5 6.5 + 6.5 6.5 + 6.5 6.5 + 6.5 0.6 × 4 1.1 + 1.1 + 1.1 + 1.1 90.0 100
AP4201HT8 AP4201T8 400-3-50 342 457 9.5 + 9.5 6.5 + 6.5 6.5 + 6.5 6.5 + 6.5 0.6 × 4 1.1 + 1.1 + 1.1 + 1.1 92.0 110
AP4401HT8 AP4401T8 400-3-50 342 457 9.5 + 9.5 9.5 + 9.5 6.5 + 6.5 6.5 + 6.5 0.6 × 4 1.1 + 1.1 + 1.1 + 1.1 94.0 110
AP4601HT8 AP4601T8 400-3-50 342 457 9.5 + 9.5 9.5 + 9.5 9.5 + 9.5 6.5 + 6.5 0.6 × 4 1.1 + 1.1 + 1.1 + 1.1 96.0 110
AP4801HT8 AP4801T8 400-3-50 342 457 9.5 + 9.5 9.5 + 9.5 9.5 + 9.5 9.5 + 9.5 0.6 × 4 1.1 + 1.1 + 1.1 + 1.1 98.0 110
Legend
MCA Minimum circuit current, A
FLA Full load current, A
MOCP Maximum overcurrent protection current, A
kW Rated fan motor output, kW
RLA Rated load current, A
Note: RLA is based on the following conditions:
Indoor temperature: 27°C db/19°C wb
Outdoor temperature: 35°C db