Toshiba HFC R-410A Air Conditioner User Manual


 
24
Capacity correction for frosting on the outdoor heat exchanger (heating mode)
Correct the heating capacity when frost was found on the outdoor heat exchanger.
Heating capacity = Capacity after correction of outdoor unit × correction value of capacity resulting from frost
(Capacity after correction of outdoor unit: Heating capacity calculated in the previous
section.)
Capacity correction for frosting on the outdoor heat exchanger
Capacity correction value
Outdoor air wet bulb temperature (°C)
Capacity calculation for each indoor unit
Capacity for each indoor unit =
Capacity after correction of outdoor unit ×
Operating temperature range
In cooling mode In heating mode
Required standard capacity of indoor unit
Total value of standard indoor unit capacity
Usable range
(in pull-down mode)
Usable range
(in warming-up mode)
Rated conditions
Cooling: Indoor air temperature 27°C db/19°C wb.
Outdoor air temperature 35°C db.
Heating: Indoor air temperature 20°C db.
Outdoor air temperature 7°C db/6°C wb.
Outdoor air dry bulb temperature (°C)
Indoor air wet bulb temperature (°C)
Continuous
operating
range
Outdoor air wet bulb temperature (°C)
Indoor air dry bulb temperature (°C)
Continuous
operating
range
The unit can be operated even if outdoor
temperature falls to -20°C. However, the warranty
only covers operation down to -15°C, as lower
temperatures are outside the operating range.
When the outdoor air temperature falls to below
-15°C, unit operation may reduce the product life.