Mitsubishi Electronics TG-2000A Air Conditioner User Manual


 
34
3) Select [OK] button.
Click the [OK] button after fully completing the ventilation unit interlocking setting.
8.7 Monitoring Screen Set-up
Set the information such as the floor name, plan view, operation block, or other items to be monitored/
displayed on the management screen of the integrated centralized control software TG-2000A.
8.7.1 Configuration Procedure and Restrictions
Check these points before setting the system configuration.
[Procedure]
1) Click the [Monitoring screen set-up] button.
Click the [Monitoring screen set-up] button in the
User Settings Group in the Initial window.
2) Click the [OK] button after checking the display
contents.
Check the information displayed and click the [OK]
button.
* When the [Cancel] button is clicked, this setting is
terminated to return to the initial screen.
The monitor display set-ups are done in the following
order.
Step1 : Set-up of model name
Step 2 : Set-up of the number of floors, and floor
name
Step 3 : Creation of a plane view
Step 4 : Set-up of floor name and G-50
Step 5 : Set-up of icon arrange and name
Step 6 : Set-up of block
8.7.2 Set-up of model name (Step 1)
Set the model name of the air conditioner unit
(outdoor unit, indoor unit, sub unit, LOSSNAY etc.)
connected to this system.
Setup the unit configuration model name
[Procedure]
1) Click the “
/
” button to select G-50 No.
Select the G-50A No. to be assigned using the
/
” buttons.
2) Select the unit to be set.
Click the units for which the same Model Name is
to be set. The selected cells are displayed in cyan
and become the objective of Model Name setup. Each time clicked, the unit is alternately selected
and removed. Multiple units can also be selected.
Note:
When the ventilation unit interlocking setting is changed on the interlocked
setting screen, it is
possible to reflect the changed contents on the G-50A system.
It is possible to set up to 16 indoor units to one interlocking ventilation unit.
When the [OK
] button is clicked, the screen to confirm whether the ventilation unit interlocking
setting is completed, is displayed.
Note:
The Charge function use this set Model name
data. When the model name is changed, the
data is updated and
control is carried out
using that data.
The Model name can be checked during
maintenance.
Monitoring screen set-up preparation screen
Set button
Model name candidate
Set-up of model name screen
G-50A setting button