27
8.5 G-50 Connection Set-up
Set the integrated centralized control software TG-2000A, number of G-50A units connected, and the
IP address. It is possible for this setting to monitor and display the option functions state of the G-50A.
8.5.1 Setting Procedure and Restrictions
Confirm the precautions and procedure before setting the G-50A connection.
Perform the check before setting the G-50A connection.
[Procedure]
1) Select the [G-50 connection set-up] button.
Click the [G-50 connection set-up] button located in
the system setting group on the initial window.
2) Select the [ON] button after confirming the display
contents.
Check the contents of the alarm displayed. When
there are not any problems found, click the [OK]
button to advance to the setting.
* When the [Cancel] button is clicked, this setting is
terminated to return to the initial screen.
Set the G-50A connection in accordance with the
following procedure.
Step 1: Number of G-50 set-up
Step 2: IP address of G-50 set-up
8.5.2 Number of G-50A set-up (Step 1)
Set the number of G-50 connected to the system.
Set-up the number of G-50A
[Procedure]
1) Click the “
/
“ buttons.
Use the “
/
“ buttons to set the number of G-50A.
Number of connectable G-50A units: 1 to 40 units
2) Click [OK] button.
When finished making settings, click the [OK] button.
* When the [Cancel] button is clicked, this setting is
terminated to return to the initial window.
8.5.3 IP address of G-50A set-up (Step 2)
Set the data of the G-50A IP address connected to
the data of the integrated centralized control
software.
Register the G-50A IP address.
[Procedure]
1) Select the G-50 No. with the “
/
“ buttons.
In this case, use the “
/
“ buttons to select the
G-50A No. for which the IP address information is
registered.
G-50 connection Set-up
Number of G-50A set-up
IP address of G-50A set-up