8.6.2 G-50A data collection (Step 1)
It is possible to collect the system information (group information, interlocking ventilation unit
setting information, etc.) set for the G-50A with the integrated centralzed control software
TG-2000A during the initial setting.
Collect the information from the G-50A during the
initial setting.
[Procedure]
1) Select the [Collecting of information from G-50]
button.
To collect the system information from the G-50A
during the initial setting, click the [Collecting of
information from G-50] button.
After completing the information collecting, the opera-
tion advances automatically to the next step. Wait a
moment, as it takes time for information collecting.
* When the [Cancel] button is clicked, this setting is
terminated to return to the initial screen.
Skip the collecting information from the G-50A.
[Procedure]
1) Select the [Next] button.
If it is not necessary to collect the information, click the [Next] button.
8.6.3 Unit composition set-up (Step 2)
It is possible to confirm and change the configuration of the unit in each G-50A.
Confirm the unit configuration.
[Procedure]
1) Select the G-50 No. with the /“ buttons.
In this case, use the /“ buttons to select the G-50A No. desired to confirm the unit
configuration.
2) Select the [OK] button after checking the unit configuration of each G-50A.
If it is not necessary to change the unit configuration of each G-50A when it is checked, click the [OK] button.
*When the [Cancel] button is clicked, this setting is terminated to return to the initial window.
Caution:
Note that using the G-50A
data collecting function may cause the system information possessed
in the TG-2000A to be completely cleared. When the information is collected,
execute the initial
setting again as it is written over the G-50A information.
It can only collect the information when all the G-50A units are connected.
It is recommended to execute this function after the test operation of the air conditioner and th
e
G-50A have been completed normally.
G-50A Data collection screen
Unit configuration address setting
window
Unit configura-
tion table:
Displays the system
configuration unit of
the G-50 concerned.
Selected unit icon:
Displays the icons (symbols)
such as the indoor unit, outdoor
unit, remote controller, system
remote controller, etc. and their
names.
G-50A Selection:
Select the G-50 No.