60 Audio Command Center Series Manual — P/N 51889:E1 6/8/2010
Installation Installation of Option Modules
5. When testing is completed, remove the FC-LPS and standoff and reinstall the screw. The
FC-LPS is not approved for permanent connection.
3.8.4 ACC-EPM External Page Module
The ACC-EPM External Page Module can be used to interface an existing nonemergency page sys-
tem with the ACC-25/50 Series panels. The connection is not supervised and the external page sys-
tem will have the lowest priority which allows the ACC-25/50 Series to override all non-fire
paging. Paging from non-emergency equipment is prohibited during AC loss conditions to pre-
serve battery power.
The External Page Module is installed by plugging the module into connector P13 which is located
in the top right corner of the main circuit board.
1. Carefully align the J1 connector on the ACC-EPM module with the P13 connector on the main
circuit board and press securely into place. Make certain the pins are properly aligned to
prevent bending or breaking of pins.
2. Secure the ACC-EPM module to the main circuit board standoff with the supplied screw.
3. Wire the external paging system to Terminal TB1 on the ACC-EPM. Refer to the
documentation supplied with the external paging system to ensure proper connection.
Plug Speaker Module Cable
into connector P2 (Step 4)
Remove mounting screw from main
circuit board and install metal
standoff (Steps 1 and 2)
Install FC-LPS Speaker
Module on metal
standoff (Step 3)
a
c
2
5
s
p
k
r
2
.
w
m
f
(Step 2) Install one metal
standoff by screwing into place
Main Circuit Board Main Circuit Board Main Circuit Board
Speaker
Module
2
5
5
0
s
p
k
s
.
w
m
f
(Step 1) Remove the mounting screw
from bottom center of main circuit board
(Step 3) Install Speaker Module
and secure with screw
Figure 3.19 Installation of Speaker Module
!
CAUTION: DISCONNECT POWER
BEFORE INSTALLING ANY MODULES, MAKE CERTAIN ALL POWER (AC AND DC) HAS BEEN
REMOVED.