Audio Command Center Series Manual — P/N 51889:E1 6/8/2010 111
MS-9600, MS-9200UDLS and MS-9200UD Programmed Activation by FACP
if an addressable device programmed to Zone 35 is activated and no other devices are active,
the message programmed for Zone 35 will be generated over speaker circuit 3 on the ACC-
25/50ZS or ACC-25/50ZST. (Refer to Table D.5 on page 109).
if an addressable device (address 09 in example below) programmed to Zone 35 is activated
and a second addressable device (address 15 in example below) programmed to Zone 36 is
activated, the highest priority message programmed to either Zone 35 or Zone 36 (Message 3
in example below) will be generated over speaker circuits 3 and 4. (Table D.5 on page 109). If
an addressable device (address 21 in example below) programmed to Zone 32 is then acti-
vated, the highest priority message programmed to Zone 32, 35, or 36 (Message 1 in example
below) will be generated over all speaker circuits. (Table D.5 on page 109).
Addressable Pull Station
Programmed to
Message 3
Zone 35
activate
Speaker Circuit 3
Addressable Pull Station
(address 21)
Programmed to
Zone 32
Message 4
(lowest priority of the three)
Message 3
(2nd highest priority of the three)
Message 1
(highest priority of the three)
Addressable Pull Station
(address 09)
Zone 35
Programmed to
Zone 36
Programmed to
Addressable Pull Station
(address 15)
activate
activate
activate
Speaker Circuit 1
Speaker Circuit 2
Speaker Circuit 3
Speaker Circuit 4
Speaker Circuit 5
Speaker Circuit 6
Speaker Circuit 7
Speaker Circuit 8