Honeywell 50ZST Smoke Alarm User Manual


 
Audio Command Center Series Manual — P/N 51889:E1 6/8/2010 125
MS-9200(E) Programmed Activation by FACP
ACC-25/50ZS & ACC-25/50ZST Switch Settings
ACC-ZPMK DIP Switch S1
Switches 1, 2, and 3 are used to configure the ACC-25/50ZS/T for operation with a specific
FACP (See Table 2.4 on page 35.)
Switch 4 - future use
Switches 5, 6, 7, and 8 - used to set the number of ACC-25/50DAZS panels installed
(See Table 2.4 on page 35.)
ACC-ZPMK Rotary Address Switches S2 and S3
The address switches must be set to ACS address 01 to communicate with the FACP. Any other
ACS devices which are set to address 01 should be in Receive Mode only.
•S2=1
•S3=0
ACC-ZSM Zone Splitter Module Switch Settings
See “ACC-ZSM Zone Splitter Module (ACC-25/50ZS & ACC-25/50ZST)” on page 41 for infor-
mation on setting these switches.
D.3.4 FACP Programming
The MS-9200(E) must be programmed to operate with the ACC-25/50ZS/T Audio Command Cen-
ter. The following table summarizes the steps involved in programming the FACP.
ACS Annunciator
The ACC-25/50ZS/T communicates with the FACP via the ACS link. Enable the ACS Annuncia-
tor as described in the MS-9200(E) manual. The ACS programming options can be accessed by
entering Programming Mode and selecting option 3=SYS from the list of programming options.
Zone Assignment
Zones must be assigned to each addressable input device in order to activate the appropriate output
device(s). Program each device to a zone as described in the appropriate FACP manual. Device
programming can be accessed by entering Programming Mode and selecting option 2=ZONE from
the list of programming options.
Note that when the ACS Annunciator option is enabled at the FACP, speaker circuits at the
ACC-25/50ZS/T are automatically assigned dedicated zone numbers (32 through 56). These zone
numbers can then be programmed to addressable input devices which will allow the input device to
activate the programmed speaker zone.
The following table lists the zone numbers that are automatically assigned to each speaker circuit.
Note that the ACC-ZSM Zone Splitter Module installed in the ACC-25/50ZST and each
ACC-25/50DAZS provides 8 Style Y (Class B) speaker circuits.
Enable the ACS annunciator at FACP refer to FACP manual Option Module Programming
Assign zones to each addressable device refer to FACP manual Point Programming
Activate individual devices to ensure proper programming compare to desired programming
Table D.6 FACP Programming Steps