Honeywell 50ZST Smoke Alarm User Manual


 
130 Audio Command Center Series Manual — P/N 51889:E1 6/8/2010
Programmed Activation by FACP MS-5UD-3/7 and MS-10UD-3/7
Switches 5, 6, 7, and 8 - used to set the number of ACC-25/50DAZS panels installed.
ACC-ZPMK Rotary Address Switches S2 and S3
The address switches can be set to any address from 01 through 08 to communicate with the FACP.
Any other ANN-BUS devices must be set to a different address.
S2=1 - 8
•S3=0
ACC-ZSM Zone Splitter Module Switch Settings
See “ACC-ZSM Zone Splitter Module (ACC-25/50ZS & ACC-25/50ZST)” on page 41 for infor-
mation on setting these switches.
ACC-FFT Fire Fighter Module Switch Setting (ACC-25/50ZST only)
See Section “SW1 - Remote Microphone Installed Switch on ACC-FFT” on page 39 for additional
information.
D.4.5 FACP Programming
The FACP must be programmed to operate with the ACC-25/50ZS or ACC-25/50ZST Audio Com-
mand Center. The following table summarizes the steps involved in programming the FACPs. A
detailed description of each step follows the table.
ANN-BUS Annunciator
The ACC-25/50ZS and ACC-25/50ZST communicate with the FACP via the ANN-BUS link.
Auto-configure the ANN-BUS Annunciator as described in the appropriate FACP manual. The
ANN-BUS programming options can be accessed by entering Programming Mode and selecting
Option Modules from the list of programming options.
Zone Assignment
Zones must be assigned to each addressable input device in order to activate the appropriate output
device(s). Program each device to a zone as described in the appropriate FACP manual. Device
programming can be accessed by entering Programming Mode and selecting Point Program from
the list of programming options.
S1 DIP Switch ON OFF
5 not used (must be set to OFF)
6 This switch works in conjunction with switches 7 & 8 to set the number of ACC-25/50DAZS panels connected
7 This switch works in conjunction with switches 6 & 8 to set the number of ACC-25/50DAZS panels connected
8 6 OFF, 7 OFF, 8 OFF = No ACC-25/50DAZS Distributed Audio Panels connected to ACC-25/50ZS/T
6 OFF, 7 OFF, 8 ON = 1 ACC-25/50DAZS Distributed Audio Panel connected to ACC-25/50ZS/T
6 OFF, 7 ON, 8 OFF = 2 ACC-25/50DAZS Distributed Audio Panels connected to ACC-25/50ZS/T
6 OFF, 7 ON, 8 ON = 3 ACC-25/50DAZS Distributed Audio Panels connected to ACC-25/50ZS/T
6 ON, 7 OFF, 8 OFF = 4 ACC-25/50DAZS Distributed Audio Panels connected to ACC-25/50ZS/T
6 ON, 7 OFF, 8 ON = 5 ACC-25/50DAZS Distributed Audio Panels connected to ACC-25/50ZS/T
Table D.9 Number of ACC-25/50DAZS Panels Installed
Enable the ANN-BUS annunciator at FACP refer to FACP manual Option Module Programming
Assign All-Call Zone (if applicable) refer to FACP manual ANN Options Programming
Program message to be generated over each speaker circuit refer to Message Assignment in following section
Activate individual devices to ensure proper programming compare to desired programming
Table D.10 FACP Programming Steps