Honeywell 50ZST Smoke Alarm User Manual


 
Audio Command Center Series Manual — P/N 51889:E1 6/8/2010 11
Audio Command Center Zone System
Up to 24 Zones @ 150W (max.)
Speaker Circuit #16
1. The FACP controls the audio system via the ACS Link or CMD
inputs on the ACC-25/50ZS
2. The Audio Riser connects the audio output of the ACC-25/50ZS to
each of the ACC-25/50DAZS(s) to distribute alarm or paging
audio.
3. The ACC-25/50ZS uses the Control Serial Link to control the
routing of the alarm or paging audio.
4. Riser conductors must be installed in accordance with the
survivability from attack by fire requirements in National Fire
Alarm Code, NFPA 72.
Speaker Circuit #9
Speaker Circuit #17
Speaker Circuit #24
ACC Control Serial Link (RS-485)
Audio Riser
Speaker Circuit #1
Speaker Circuit #8
ACC Control Serial Link (RS-485)
Automatic Control via the
ACS Link or CMD Input
ACC-25/50DAZS
ACC-25/50ZS
ACC-25/50DAZS
ACCDAZSDISTSYS2.wmf
Audio Riser