Audio Command Center Series Manual — P/N 51889:E1 6/8/2010 115
MS-9600, MS-9200UDLS and MS-9200UD Programmed Activation by FACP
Fire Fighter Telephone SLC Point Assignment
If annunciation of remote FFT locations is desired on the ACC-FFT keypad, an addressable input
device must be programmed as a PHONE type on the MS-9200UDLS or MS-9600.
Program each addressable input device as a PHONE type as described in the appropriate FACP
manual. SLC point programming can be accessed by entering Programming Mode and selecting
Point Program from the list of programming options.
The following table lists the SLC points dedicated for FFT annunciation:
FFT Number on ACC-FFT Keypad
MS-9200UDLS SLC Point Number
(ACS Address 05)
MS-9600 SLC Point Number
(ACS Address 07)
FFT Inputs can be installed only
on SLC Loop #1
1 75 135
2 76 136
3 77 137
4 78 138
5 79 139
6 80 140
7 81 141
8 82 142
9 83 143
10 84 144
11 85 145
12 86 146
13 87 147
14 88 148
15 89 149
16 90 150
17 91 151
18 92 152
19 93 153
20 94 154
21 95 155
22 96 156
23 97 157
24 98 158