CENTRAL PROCESSOR PACKAGE INSTALLATION
2-6
February 1996
Part No. 004-3039-274
Figure 2-5 COMMON GROUND BRACKET ASSEMBLY
placement of the connections on the common ground
bracket assembly. Use #4 THHN wire to connect to
the ground clamp.
#3 Lug
Connect a #6 THHN wire to lug #3 (third from
top) on the common ground bracket assembly to the
ground lug in the CPP cabinet. Refer to Figure 2-5
for the location of the ground lug in the CPP cabinet.
#4, #5 Lug
Connect a #6 THHN ground wire from lugs 4, 5,
etc. of the ground bracket assembly to the ground lug
on each console position. A ground lug and hardware
has been furnished with the cable kit for each console.
2.6 GROUNDING INSTALLATION
#1 Lug
Connect a #6 THHN bare ground wire to the TOP
RIGHT (first) copper lug on the common ground
bracket assembly to all RTL kits (make this by taking
a length of the #6 THHN wire and stripping it). If
multiple surge arrestor boxes are used, run the #6
THHN wire through the lugs of all boxes in a straight
line. Tighten all clamps securely using the proper size
screwdriver ( 1/4" flatblade).
#2 Lug
It is very important to connect the earth ground
wire to lug #2, the lug opposite the CPP Cabinet lug
and RTL kits lugs. Refer to Figure 2-5 for acorrect