Weil-McLain GV90+ Boiler User Manual


 
Part number 550-142-054/0411
85
GV90+ gas-fired water boilerBoiler Manual
Troubleshooting (continued)
CHART 5
FLAME & POWER lights flashing
Electrical shock hazard — Wherever you see TURN OFF POWER, follow the instructions. Failure to follow
instructions could result in severe personal injury, death or substantial property damage.
Open manual gas valve.`
Restart boiler, following Operating instructions on boiler
(see Figure 76, page 66).
Check for proper operation (per normal sequence of
operation).
Boiler should now operate normally.
Original flashing FLAME light caused by igniter not
operating properly.
See normal sequence of operation (Figure 75, page 65).
Boiler should now operate normally.
Original flashing FLAME light caused by gas valve not
operating properly.
See normal sequence of operation (Figure 75, page 65).
Replace IBC.
Retest.
Call your local Weil-McLain
sales representative.
Are manual main shutoff valve and gas valve turned on?
No Yes
Check gas valve harness wires and check for tight wiring connec-
tions on gas valve and IBC. Repair/replace as necessary.
Recycle boiler by thermostat or service switch (holding power off for
at least 45 seconds).
Thermostat should call for heat and appropriate zone valves close.
During step 5 of normal sequence of operation (Figure 75, page 65),
is there 24 VAC across gas valve terminals?
No Yes
Check and/or replace igniter.
Recycle boiler by thermostat or service switch. Thermostat should
call for heat and appropriate zone valves close.
Wait 5 minutes.
Are FLAME & POWER lights flashing?
No Yes
Check and/or replace gas valve.
Recycle boiler by thermostat or service switch. Thermostat should
call for heat and appropriate zone valves close.
Wait 5 minutes.
Are FLAME & POWER lights flashing?
No Yes