Weil-McLain GV90+ Boiler User Manual


 
Part number 550-142-054/0411
65
GV90+ gas-fired water boilerBoiler Manual
Figure 75 Integrated boiler control (IBC) sequence of operation — status light indications
STEPS
(After Step 8, the cycle goes back to Step 1)
Call for
Heat?
POWER TSTAT
CIRC
LIMIT PRESS
SWITCH
FLAME
Timing
1. Standby
Waiting for call for heat
NO
2. Call for heat
Circulator on
YES
3. Limit circuit
Limit controls closed
Block switch contacts closed
Blower on
YES
4. Pressure circuit
Pressure switch contacts closed
Ignitor glows
YES
30 sec
5. Flame proven
Gas valve open
Ignitor remains on
YES
6 sec
6. Limit cycle
Limit circuit open
Gas valve closed
Blower off after postpurge
YES
30 sec
7. Flame outage *
Flame out
YES
8. Thermostat satisfied
Circulator off
Blower postpurge
Return to Step 1
NO 30 sec
= ON
= OFF
* If flame is not proven in 4 seconds, boiler recycles 2 times to retry for ignition before going into lockout. Recycle igniter timing
is 30 seconds. Postpurge and prepurge are performed on every cycle. In event of lockout, ignition control will automatically
restore sequence of operation after either:
• 1 hour waiting period.
• Opening and closing of thermostat circuit.
• Removal of 120 VAC power for at least 45 seconds