Weil-McLain GV90+ Boiler User Manual


 
Part number 550-142-054/0411
67
GV90+ gas-fired water boilerBoiler Manual
Figure 77 Service and maintenance schedules
Service technician
(see following pages for instructions)
Owner maintenance
(see following pages for instructions)
Annnual start-up
General:
• Address reported problems, page 68.
• Inspect boiler area, page 68.
• Inspect boiler interior, page 68.
• Inspect condensate drain system, page 68.
• Inspect all piping for leaks, page 68.
• Inspect gas piping, page 68.
• Inspect the water system, page 68.
• Check water system chemistry, page 68
• Inspect expansion tank, page 69.
• Inspect air openings, page 69.
• Inspect vent system and air piping,
page 69.
• Inspect boiler heating surfaces, page 69.
• Inspect igniter, page 69.
• Inspect recuperator, page 70.
• Inspect temperature mixing system,
page 70.
• Inspect limit controls and cutoffs, page 70.
• Inspect gauges, page 70.
• Inspect blower motor, page 70.
• Inspect oiled-bearing circulators, page 70.
• Inspect boiler relief valve, page 71.
Additional if combustion or
performance indicates the need:
• Follow procedures under Cleaning boiler
heating surfaces, page 72 to access boiler
components listed below.
• Clean heat exchanger.
• Remove and clean burner using
compressed air only.
• Vacuum the blower.
Review:
• Review with owner.
Daily
• Check boiler area
• Check air openings
• Check pressure gauge
Monthly
• Check boiler interior piping
• Check venting system
• Check air vents
• Check condensate drain system
• Check relief valve
Periodically
• Test low water cutoff (if used)
• Clean vent termination/air intake
screens
Every 6 months
• Oil blower motor
• Operate relief valve
End of season
• Shut down procedure
Annual start-up and general maintenance schedule
Follow the Service and maintenance procedures given throughout
this manual and in component literature shipped with the boiler.
Failure to perform the service and maintenance could result in
damage to the boiler or system. Failure to follow the directions
in this manual and component literature could result in severe
personal injury, death or substantial property damage.
The boiler contains ceramic fiber
and fiberglass materials. Use care
when handling these materials per
instructions on page 107 of this
manual. Failure to comply could
result in severe personal injury.