Weil-McLain GV90+ Boiler User Manual


 
Part number 550-142-054/0411
83
GV90+ gas-fired water boilerBoiler Manual
Troubleshooting (continued)
CHART 3
LIMIT & POWER lights flashing
Electrical shock hazard — Wherever you see TURN OFF POWER, follow the instructions. Failure to follow
instructions could result in severe personal injury, death or substantial property damage.
This is a LOCKOUT condition. The return water temperature
sensor has signaled a temperature higher than 240 °F, but the
boiler limit circuit is closed (indicating that the limit control circuit
did not catch the over-temperature condition). This is probably
an indication of a failure of the boiler limit control and possibly
the block temperature switch as well.
TURN OFF POWER to boiler at 120 VAC service switch.
Remove CONTROL CIRCUIT plug from IBC receptacle (Fig-
ure 93, page 78, Item 5).
Remove a wire from one of the limit control spade connec-
tors.
Connect an ohmmeter across the left and right pins on the
center row of the limit circuit harness.
Does the ohmmeter indicate a shorted wire harness (zero ohms)?
Yes No
Replace control wiring harness.
Retest.
Replace water temp sensor.
Retest.
Close the external manual gas valve.
Remove one wire from the limit control space
connector.
Set a thermostat to call for heat. Then turn on
power to the boiler at the 120 VAC service switch.
The boiler system circulator should come on and
the IBC should try to cycle the boiler.
Allow the boiler circulator to run to cool off boiler
and system water.
After the boiler and system water have cooled,
turn off power at the 120 VAC service switch and
open the external manual gas valve.
Replace IBC.
Retest.
Replace limit control and
block temperature switch.
Retest.
Reconnect CONTROL CIRCUIT plug to IBC.
Remove WATER TEMP SENSOR plug from IBC receptacle
(Figure 93, page 78, Item 6).
Connect an ohmmeter across the plug pins to check the sen-
sor resistance.
Does the ohmmeter indicate a shorted sensor (zero ohms)?
Yes No
Set limit control knob to its minimum setting. Replace wire to
limit control spade connector.
Set a thermostat to call for heat.
Turn on power at 120 VAC service switch.
IBC should cycle boiler on and begin heating.
The limit control should shut off the gas valve when the
temperature at the boiler pressure/temperature gauge has
reached no more than about 20 °F higher than the limit
switch setting.
Does limit control shut off gas correctly?
Yes No
Is boiler hot?
Yes No