Raypak 120 Boiler User Manual


 
30
Stainless Steel 3” Vent System
1
US + CANADA
Vent System - Room Air independent Operation (Sealed Combustion Operation) - Fig. 12-14-15-17
Vent System diameter 3”
Vent system material Stainless steel
Two pipes vent adaptors (included with the boiler) - -
adaptor 80 mm > 3” (included with the boiler 1 pcs) for flue - -
adaptor 80 mm > 3” for intake air Field supplied Order No.
Combustion air intake vent material
3
Field supplied Order No.
ULC/UL listed
1
Stainless steel Vent material
45° elbow EqL = 2 ft / 0,6m Field supplied Order No.
90° elbow EqL = 3 ft / 0,9m
Bird Screen c/w Termination Field supplied Order No.
Venting support
2
dia. 3” Field supplied Order No.
1
stainless steel vent material must be ULC/UL listed, stainless steel AL29-4C
®
for category IV boilers. Sources FasNseal – Protech
System Inc.
2
Order Mounting Clip for each straight length of vent pipe installed, boiler can not support weight of vent system
3
allowable material for combustion air ABS – CPVC – PVC or stainless steel
- Do not exceed maximum equivalent vent length.
- Always follow XPak Venting System Installation Instructions.
Tab. 7
Stainless Steel Vent System
1
US + CANADA
Vent System - Room Air Dependent Operation - Fig. 13-16-18
Vent System diameter 3”
Vent system material Stainless steel
Adaptor for room air dependent operation
3
013102 Order No.
adaptor 80 mm > 3” (included with the boiler 1 pcs) - -
ULC/UL listed
1
Stainless steel Vent material
45° elbow EqL = 2 ft / 0,6m Field supplied Order No.
90° elbow EqL = 3 ft / 0,9m
Bird Screen c/w Termination Field supplied Order No.
Venting support
2
dia. 3” Field supplied Order No.
1
Stainless steel vent material must be ULC/UL listed, stainless steel AL29-4C
®
for category IV boilers. Sources FasNseal –
Protech System Inc.
2
Order Mounting Clip for each straight length of vent pipe installed, boiler can not support weight of vent system
3
Provide a proper air opening in the room (size according indication pg. 7)
- Do not exceed maximum equivalent vent length.
- Always follow XPak Venting System Installation Instructions.
Tab. 8