03_NVspec_ver304e
2-6.LOSSNAY
(1)LOSSNAY interlocks with the indoor unit.(*1,3)
Indoor[1]-[50]
Network Variables
nv22n
nvoAlarm_n
SNVT_switch
(*4)
nv23n
nvoErrCode_n
SNVT_count
nv24n
nvoErrAdrs_n
SNVT_count
(2)LOSSNAY is operated from L
ONWORKS.(*5,6,7)
Indoor[1]-[50]
Network Variables
nv1n
nviOnOff_n
SNVT_switch
nv2n
nvoOnOff_n
SNVT_ switch
(*4) nv7n
nviLCMode_n
SNVT_switch
nv8n
nvoLCMode_n
SNVT_switch
(*4)
nv9n
nviFanSpeed_n
SNVT_switch
nv10n
nvoFanSpeed_n
SNVT_switch
(*8,9,10) nv11n
nviProOnOff_n
SNVT_switch
nv12n
nvoProOnOff_n
SNVT_switch
(*8,9,10)
(*11) nv19n
nviFiltReset_n
SNVT_switch
nv20n
nvoOnTime_n
SNVT_time_hour
(*11)
nv22n
nvoAlarm_n
SNVT_switch
(*4)
nv23n
nvoErrCode_n
SNVT_count
nv24n
nvoErrAdrs_n
SNVT_count
nc29n
nvoGroupNo_n
SNVT_count
(*12)
Notes:
*1: stencil for LonMaker:iLOSSNAY[1]-[50]
*2: "n" of the network variable shows M-NET address of LOSSNAY.
*3: LOSSNAY is not controlled from a LONWORKS network.
*4: It may be unable to be used by the system configuration of air-conditioners units or the model of LOSSNAY.
*5: LOSSNAY is controlled from a LONWORKS network.
*6: stencil for LonMaker:LOSSNAY[1]-[50]
*7: Please turn ON the switch(SW1-5) when LOSSNAY is operation from LONWORKS.(Factory setting "OFF")
*8: There is a case which cannot be used with the system configuration of the air-conditioners units.
*9: It is possible to use with an "MA" remote controller.
*10: For the use of this function, turn ON the switch(SW1-1) on LM ADAPTER.(Factory setting "OFF")
*11: For the use of this function, turn ON the switch(SW1-8) on LM ADAPTER.(Factory setting "OFF")
*12: It is possible to use with other system controller.
WSN02-2124 - 9 -