Mitsubishi Electronics LMAP03U-E Air Conditioner User Manual


 
03_NVspec_ver304e
26n
Thermo On/Off state_1
network output SNVT_state nvoThermo_n;
This output network variable indicates the On/Off state of the indoor unit , the thermostat and the auxiliary
heater for heating.
This variable is used to calculate the electric charge.
Valid Range
bit[2] bit[1] bit[0] status
--
0 Indoor OFF
--
1 Indoor ON
0
Indoor thermostat OFF
1
Indoor thermostat ON
0
--
Supplementary heater OFF
1
--
Supplementary heater ON
*The value is 0 while LM ADAPTER is initialized.
When Transmitted
This variable is transmitted promptly when the state changes.
This variable is output by the ncilnitStartTm (Initialize Start Time) at the powering of LM ADAPTER.
Update Rate
The value designated by nciMinOutTm (Minimum Send Time) is valid.
Default Service Type
Acknowledged
NOTE: This output value is not the addition value or proportional division value of electric charge.
This variable outputs a value now. It is necessary to perform addition and proportional division based on this
output value.
26n
Thermo On/Off state 2
network output SNVT_switch nvoThermo_n;
This output network variable indicates the On/Off state of the indoor unit.
This variable is used to calculate the electric charge.
Valid Range
SW1-7OFF SW1-7O
state value state value
Indoor thermostat OFF 0 0 0 0
Indoor thermostat ON 1 0 1 100%
*The value is 0 while LM ADAPTER is initialized.
When Transmitted
This variable is transmitted promptly when the state changes.
This variable is output by the ncilnitStartTm (Initialize Start Time) at the powering of LM ADAPTER.
Update Rate
The value designated by nciMinOutTm (Minimum Send Time) is valid.
Default Service Type
Acknowledged
NOTE: This output value is not the addition value or proportional division value of electric charge.
This variable outputs a value now. It is necessary to perform addition and proportional division based on this
output value.
Thermostat State
WSN02-2124 - 27 -