37
Local Display_1
network input config SNVT_switch nciRmDsp_1;
This configuration property defines the presence of the automatic actual operation mode display on the local
remote controller.
The value is set according to nviRmLck (Request Simplified Locking) and nviRmLim (Request Limit Temperature
Setting Range).
Valid Range
SW1-7OFF SW1-7O
state value state value
0 not used
0 not used
else not used
1 (*1) 0
no display 1 not used
1 (*1) 0.5% - 100% (*2)
*1:The setting to state=0x02-0xFE is interpreted as state=0x01.
The setting to state=0xFF is invalid.
*2:The setting to over 100% is interpreted as 100%.
Default Value
0(display)
NOTE: It is possible to use with an "ME" remote controller.
38
Local Display_2
network input config SNVT_switch nciRmDsp_2;
This configuration property defines the presence of the automatic actual operation mode display on the local
remote controller.
The value is set according to nviRmLck (Request Simplified Locking) and nviRmLim (Request Limit Temperature
Setting Range).
Valid Range
SW1-7OFF SW1-7O
state value state value
0 not used
0 not used
else not used
1 (*1) 0
no display 1 not used
1 (*1) 0.5% - 100% (*2)
*1:The setting to state=0x02-0xFE is interpreted as state=0x01.
The setting to state=0xFF is invalid.
*2:The setting to over 100% is interpreted as 100%.
Default Value
0(display)
NOTE: It is possible to use with an "ME" remote controller.
Display
display
display
display