Mitsubishi Electronics LMAP03U-E Air Conditioner User Manual


 
03_NVspec_ver304e
9
Collective Defrosting State
network output SNVT_switch nvoDefrost;
This network variable indicated the defrosting state (collective) of indoor unit and outdoor unit.
Valid Ran
g
e
SW1-7OFF SW1-7O
state value state value
Normal 0 0 0 0
defrosting 1 0 1 100%
*The value is 0 while LM ADAPTER is initialized.
When Transmitted
This variable is transmitted promptly when the state changes.
Update Rate
The maximum update rate is not available.
Default Service Type
Acknowledged
12
Time Stamp
network input SNVT_time_stamp nviRmTime;
This input network variable sets the local remote controller's time.
The time is collectively set for all remote controllers (for which the time can be set) connected to M-NET.
Valid Range
year not used0:constantly
month not used0:constantly
day not used0:constantly
hour 0 to 23
minute 0 to 59
second 0 to 59
Default Value
The value is 0 while LM ADAPTER is initialized.
NOTE: The time is reset when the local remote controller's power is turned OFF, so the time must be set periodically.
unit state
WSN02-2124 - 34 -