Mitsubishi Electronics LMAP03U-E Air Conditioner User Manual


 
03_NVspec_ver304e
24n
Error Unit Address
network output SNVT_count nvoErrAdrs_n;
This output network variable indicates the indoor unit's address.
If an error occurs in an outdoor unit, the indoor unit will also stop with an error. Thus, the error will be output
from all indoor units in the same refrigerant system. (However indoor units under stopping are excluded.)
Valid Range
0255 = Error Unit Address
65,535 = Normal
*The value is 0 while LM ADAPTER is initialized.
When Transmitted
This variable is transmitted promptly as the state changes.
This variable is also transmitted as the state changes by the operation from the local side such as a local
remote controller.
This variable is output by the ncilnitStartTm (Initialize Start Time) at the powering of LM ADAPTER.
Update Rate
The maximum update rate is not available.
Default Service Type
Acknowledged
NOTE:
1: The release of the indoor unit nvoErrAdrs_n(Error Unit Address) results in the "Off" command
of the nviOnOff_n (Request On/Off).
For the nvoErrAdrs_n(Error Unit Address) when the indoor unit is under stopping, transmit "Off",after transmitting "On".
2: The error is not output when the indoor unit is stopped, so always use together with the local remote controller
or system controller.
WSN02-2124 - 26 -