Mitsubishi Electronics LMAP03U-E Air Conditioner User Manual


 
03_NVspec_ver304e
13
Request Limit Temperature Setting Range
network input SNVT_switch nviRmLim;
This input network variable changes the local remote controller's temperature setting range.
The set temperature range is set with nciCoolLrSetP (cool/dry lower limit value setting), and nciHeatUpSetP
(Upper Setpoint Heating).
The displayed details are set with nciRmDsp_1 (Local Display 1) and nciRmDsp_2 (Local Display 2).
Valid Range
SW1-7OFF SW1-7O
state value state value
0 not used
0 not used
else not used
1 (*1) 0
1 not used
1 (*1) 0.5% to 100% (*2)
*1:The setting to state=0x02-0xFE is interpreted as state=0x01.
The setting to state=0xFF is invalid.
*2:The setting to over 100% is interpreted as 100%.
* The details displayed on the local remote controller will be set at each update regardless of the "state field" value.
Default Value
A default value is determined by the setting value of local remote controller.
This variable become state=0 and value = 0 until the value is updated after the power supply of LM ADAPTER.
NOTE:
1
:
It is possible to use with an "MA" remote controller.
2
:
The range is set collectively for all remote controllers (for which range can be set) connected to M-NET.
14
Request Simplified Locking
network input SNVT_switch nviRmLck;
This input network variable sets the simple lock for the local remote controller operations.
The simple lock range is set with nciRmOpLck (Local Operation Lock).
The displayed details are set with nciRmDsp_1 (Local Display 1) and nciRmDsp_2 (Local Display 2).
The simple lock is set collectively for all remote controllers (for which simple lock can be set) connected to M-NET.
Valid Range
SW1-7OFF SW1-7O
state value state value
0 not used
0 not used
else not used
1 (*1) 0
1 not used
1 (*1) 0.5% to 100% (*2)
*1:The setting to state=0x02-0xFE is interpreted as state=0x01.
The setting to state=0xFF is invalid.
*2:The setting to over 100% is interpreted as 100%.
* The details displayed on the local remote controller will be set at each update regardless of the "state field" value.
Default Value
A default value is determined by the setting value of local remote controller.
This variable become state=0 and value = 0 until the value is updated after the power supply of LM ADAPTER.
NOTE:
1
:
It is possible to use with an "MA" remote controller.
2
:
The range is set collectively for all remote controllers (for which range can be set) connected to M-NET.
enable
Change of the Simplified Locking
disable
Change of the setting Range
enable
disable
WSN02-2124 - 35 -