Mitsubishi Electronics LMAP03U-E Air Conditioner User Manual


 
03_NVspec_ver304e
21
Send Heartbeat_1
network input config SNVT_time_sec nciSndHrtBt_1;
This configuration property defines the time between the previous and next updating.
When the set time is elapsed from the automatic update or change output of the previous
nvoOnOff_n (On/Off Run State), automatic updating will be commenced.
The objective variables are given below.
 ・nvoOnOff_nOn/Off run state
 ・nvoMode_nMode state
 ・nvoSetP_nSetPoint state
 ・nvoLCMode_nLOSSNAY Mode state
 ・nvoFanSpeed_nFanspeed state
Valid Range
The valid range covers from 600.0 to 6540.0 seconds (per 60 seconds).
The setting to 0.0 or 6553.5 seconds makes the automatic updating invalid.
The setting to 0.1 - 599.9 seconds results in 600.0seconds.
The setting to 6540.1 - 6553.4 seconds results in 6540.0 seconds.
Default Value
6553.5 seconds without automatic update)
22
Send Heartbeat_2
network input config SNVT_time_sec nciSndHrtBt_2;
This configuration property defines the time between the previous and next updating.
When the set time is elapsed from the previous updating, automatic updating will be commenced.
The objective variable is given below.
 ・nvoSpaceTemp_nSpace Temperature
Valid Range
The valid range covers from 600.0 to 6540.0 seconds (per 10 seconds).
The setting to 0.0 or 6553.5 seconds makes the automatic updating invalid.
The setting to 0.1 - 599.9 seconds results in 600.0 seconds.
The setting to 6540.1 - 6553.4 seconds results in 6540.0 seconds.
To obtain the output within 10 minutes, set the connecting indoor unit to 30 sets or less.
Please turn ON the switch(SW1-3) on LM ADAPTER.(Factory setting "OFF")
The valid range in this case becomes as 60.0 - 6540.0 seconds (per 10 seconds).
The setting to 0.0 or 6553.5 seconds makes the automatic updating invalid.
The setting to 0.1 - 59.9 seconds results in 60.0 seconds.
The setting to 6540.1 - 6553.4 seconds results in 6540.0 seconds.
Default Value
6553.5seconds (without automatic update)