Mitsubishi Electronics LMAP03U-E Air Conditioner User Manual


 
03_NVspec_ver304e
18
Initialize Start Time
network input config SNVT_time_sec nciInitStartTm
This configuration property defines the time to start the output when the output network variables change
at LM ADAPTER power ON.
The objective network variables are given below.
 ・nvoOnOff_nOn/Off run state
 ・nvoMode_nMode state
 ・nvoSetP_nSetPoint state
 ・nvoAlarm_nAlarm state
 ・nvoErrCode_nError Code
 ・nvoErrAdrs_nError Unit Address
 ・nvoThermoSt_nThermo On/Off state_1
 ・nvoThermo_nThermo On/Off state_2
 ・nvoAllOnOffCollective On/Off state
 ・nvoAllOffEmergency state
 ・nvoAllAlarm(Collective Alarm for Indoor Unit)
 ・nvoAllAlarmLMAP(Collective Alarm for LM ADAPTER)
Valid Range
The valid range covers from 0.0,1200.0 to 3600.0 seconds (per 60 seconds).
The setting to 0.0 or 6553.5 seconds makes the initial output time setting invalid.
The setting to 0.1 - 1199.9 seconds results in 1200.0 seconds.
The settin
g
to 3600.1 6553.4 seconds results in 3600.0 seconds.
Default Value
6553.5 seconds (Setting invalid)
WSN02-2124 - 38 -