03_NVspec_ver304e
5.Configuration Properties
15
Minimum Send Time
network input config SNVT_time_sec nciMinOutTm;
This configuration property defines the minimum send time between the output network variables.
The objective network variables are given below.
Transmitting time is secured per indoor unit.
・nvoOnOff_n(On/Off run state)
・nvoMode_n(Mode state)
・nvoSetP_n(SetPoint state)
・nvoLCMode_n(LOSSNAY Mode state)
・nvoFanSpeed_n(FanSpeed state)
・nvoProOnOff_n(Local Prohibit On/Off state)
・nvoProMode_n(Local Prohibit Mode state)
・nvoProSetP_n(Local Prohibit SetPoint state)
・nvoThermoOff_n(Forced Thermostat OFF state)
・nvoOnTime_n(Filter Run Time)
・nvoSpaceTemp_n(Space Temperature)
・nvoAlarm_n(Alarm state)
・nvoErrCode_n(Error Code)
・nvoErrAdrs_n(Error Unit Address)
・nvoThermoSt_n(Thermo On/Off state_1)
・nvoThermo_n(Thermo On/Off state_2)
Transmitting time is secured per indoor unit.
・nvoAllOnOff(Collective On/Off state)
・nvoAllOff(Emergency state)
・nvoAllPro(Collective Local Prohibit state)
・nvoDefrost(Collective Defrosting state)
・nvoAllAlarm(Collective Alarm for Indoor Unit)
・nvoAllAlarmLMAP(Collective Alarm for LM ADAPTER)
Valid Range
The valid range covers from 1.0 to 600.0 seconds (per 1 second).
The setting to 0.0 or 6553.5 seconds makes the minimum send time setting invalid.
The setting to 0.1 - 0.9 seconds results in 1.0 second.
The setting to 600.1 - 6553.4 seconds results in 600.0 seconds.
Default Value
6553.5 seconds (Setting invalid)
WSN02-2124 - 36 -