Mitsubishi Electronics LMAP03U-E Air Conditioner User Manual


 
03_NVspec_ver304e
17n
Re
q
uest Forced Thermostat OFF
network input SNVT_switch nviThermoOff_n;
This input network variable is used to forcibly change indoor unit to the thermo OFF state (Fan mode).
The forced thermo OFF setting will be cancelled when the time set with nciRcvHrtBt_2 (Receive Heartbeat 2)
elapses, so periodic updating is required.
Valid Range
SW1-7OFF SW1-7O
state value*1 state value
0 1% to 100% (*3) 0 not used
else 1% to 100% (*3) 1 (*2) 0
0 0% to 0.5%
else 0% to 0.5%
1 not used
*1:The value field is set in 100% usually.
*2:The setting to state=0x02-0xFE is interpreted as state=0x01.
The setting to state=0xFF is invalid.
*3:The setting to over 100% is interpreted as 100%.
Default Value
The default value is determined by the state of the air conditioner indoor unit).
This variable becomes value = 0 until the value is updated after the power supply of LM ADAPTER.
18n
Forced Thermostat OFF state
network output SNVT_switch nvoThermoOff_n;
This output network variable indicates the current forced thermo OFF state of the indoor unit.
Valid Range
SW1-7OFF SW1-7O
state value state value
disable 0 0 0 0
enable 1 0 1 100%
   *The value is 0 while LM ADAPTER is initialized.
When Transmitted
This variable is transmitted promptly as the state changes.
It is also transmitted as the state changes by the operation from the local side such as a local remote controller.
Update Rate
The maximum update rate is not available.
Default Service Type
Acknowledged
1 (*2)
Thermostat OFF
disable
Thermostat OFF
0.5% to 100% (*3)enable
WSN02-2124 - 22 -