Space Temperature
network output SNVT_temp_p nvoSpaceTemp_n;
This output network variable indicates the state of the indoor temperature.
Valid Range
Output range -10 50
Temperature unit 0.1
*The value is 0 while LM ADAPTER is initialized.
When Transmitted
This variable is transmitted when the indoor temperature changes by more than 1. (However , it will not be
transmitted for changes within 10 minutes.)
This variable is output when the state change is more than the change width set in nciAnalogWidth
(indoor temperature change width setting). (Note that changes within 10 minutes will not be output.)
*To obtain the output within 10 minutes, please refer to the nciSndHrtBt_2 (Send Heartbeat_2) and the
nciAnlgMonTm(Monitoring Time).
Update Rate
The value designated by nciSndHrtBt_2 (Send Heartbeat_2) and nciMinOutTm (Minimum Send Time) is valid.
Default Service Type
Acknowledged
NOTE:
1
:
Indoor temperature is outputted while an indoor unit stops. However,please usually use it for temperature
measurement only during operation. It may not become a normal value while a fan stops.