Mitsubishi Electronics LMAP03U-E Air Conditioner User Manual


 
03_NVspec_ver304e
2
Collective On/Off state
network output SNVT_switch nvoAllOnOff;
This output network variable collectively indicates the current On/Off state of the indoor units or ventilators
(during independent non-interlocked operation).
Valid Range
SW1-7OFF SW1-7O
state value state value
All Off 0 0% to 100% 0 0
One or more sets are ON or in test run
1 0% to 100% 1 100%
*The value is 0 while LM ADAPTER is initialized.
When Transmitted
This variable is transmitted promptly when the state changes.
It is also transmitted as the state changes by the operation from the local side such as a local remote controller.
This variable is output by the ncilnitStartTm (Initialize Start Time) at the powering of LM ADAPTER.
Update Rate
The maximum update rate is not available.
Default Service Type
Acknowledged
Collective Unit state
WSN02-2124 - 31 -