03_NVspec_ver304e
1-3.Functions
Operation Request All Off
nv1
Stops the operation of all air conditioners.
The ON/OFF operation is invalid during emergency stop.
Request On/Off
nv1n Run and stop operation.
Request Mode
nv3n Sets the operation mode.
Setpoint
nv5n Sets the temperature.
Request LOSSNAY Mode
nv7n Sets the LOSSNAY operation mode.
Request FanSpeed
nv9n Sets the fan speed.
Request Local Prohibit On/Off
nv11n Sets the local remote controller to operation prohibit (On/Off).
Request Local Prohibit Mode
nv13n Sets the local remote controller to operation prohibit (operation mode).
Request Local Prohibit SetPoint
nv15n Sets the local remote controller to operation prohibit (temperature setting).
Request Collective Local Prohibit
nv4
Sets the local remote controllers of all air conditioners to operation prohibit
(On/Off, operation mode, temperature setting).
Request Forced Thermostat OFF
nv17n Forcibly turns the air conditioner thermostat OFF.
Filter Sign Reset
nv19n The run time (for filter) of air conditioner is reset.
Time Stamp
nv12 Sets the local remote controller time.
Request Limit Temperature Setting Range
nv13 Sets the temperature setting range of local remote controller.
Request Simplified Locking
nv14
Sets the local remote controller switch's simple lock, and displays the mode and
intake temperature.
Monitor Emergency state
nv3 Output the emergency stop state.
On/Off state
nv2n Outputs the On/Off state.
Collective On/Off state
nv2 Outputs the On/Off state for all air conditioners.
Mode state
nv4n Outputs the operation mode setting state.
Setpoint State
nv6n Outputs the temperature setting state.
LOSSNAY Mode State
nv8n Outputs the LOSSNAY operation mode setting state.
FanSpeed state
nv10n Outputs the fan speed setting state.
Local Prohibit On/Off State
n12n Outputs the local remote controller operation prohibit (On/Off) state.
Local Prohibit Mode State
nv14n Outputs the local remote controller operation prohibit (operation mode) state.
Local Prohibit SetPoint State
nv16n
Outputs the local remote controller operation prohibit (temperature setting)
state.
Collective Local Prohibit State
nv5 Outputs the local remote controller collective operation prohibit state.
Forced Thermostat OFF State
nv18n Outputs the forced thermostat OFF state.
Run Time for Filter
nv20n Outputs the run time (for filter) of air conditioner.
Space Temperature State
nv21n Outputs the intake temperature of air conditioner.
Defrost State
nv9 Outputs the defrosting state of indoor unit or outdoor unit.
Group Number
nv29n Outputs the group number of the indoor unit.
Alarm State
nv22n Outputs the presence of air conditioner errors.
Collective Alarm for Indoor Unit
nv6 Outputs the presence of errors in all air conditioners.
Collective Alarm for LM ADAPTER
nv7
Outputs the presence of communication errors between the LM ADAPTER and
air conditioner.
Error Code
nv23n Outputs the presence of air conditioner errors content (error code).
Error Address
nv24n Outputs the error source (M-NET address) when an air conditioner error occurs.
Thermo On/Off state_1 (*1)
nv25n Outputs the air conditioner operation, thermostat and auxiliary heater states.
Thermo On/Off state_2 (*1)
nv26n Outputs the thermostat state.
Model Code (*1)
nv28n Outputs the air conditioner model code.
Note
*1: This product does not have a charge function.
The charge (apportioning) function must be prepared separately in the master system.
Item
n
v
No.
Description
WSN02-2124 - 3 -