Request Local Prohibit SetPoint
network input SNVT_switch nviProSetP_n;
This input network variable is used to prohibit the temperature setpoint change of the local remote controller connected
to the indoor unit.
Instructions according to this network variable in under the prohibition of collective operation (nvoAllPro outputs
"Enable") are held.
The operation prohibit setting will be cancelled when the time set with nciRcvHrtBt_1 (Receive Heartbeat 1) elapses ,
so periodic updating is required.
Valid Range
SW1-7OFF SW1-7O
state value state value
0 not used 0 not used
else not used 1 (*1) 0
1 not used 1 (*1) 0.5% to 100% (*2)
*1:The setting to state=0x02-0xFE is interpreted as state=0x01.
The setting to state=0xFF is invalid.
*2:The setting to over 100% is interpreted as 100%.
Default Value
The default value permit temperature setpoint change for local remote controller.
This variable becomes value = 0 until the value is updated after the power supply of LM ADAPTER.
NOTE:
1
:
For the use of this function, turn ON the switch (SW1-1) on LM ADAPTER.(Factory setting "OFF")
2
:
It is possible to use with an "MA" remote controller.
16n
Local Prohibit SetPoint state
network output SNVT_switch nvoProSetP_n;
This output network variable indicates the prohibit/permit of the temperature setting for the local remote controller
connected to the indoor unit or ventilator.
Valid Range
SW1-7OFF SW1-7O
state value state value
Permit 0 0 0 0
Prohibit 1 0 1 100%
   *The value is 0 while LM ADAPTER is initialized.
When Transmitted
This variable is transmitted promptly as the state changes.
Update Rate
The maximum update rate is not available.
Default Service Type
Acknowledged
NOTE:
1
:
For the use of this function, turn ON the switch (SW1-1) on LM ADAPTER.(Factory setting "OFF")
2
:
It is possible to use with an "MA" remote controller.