03_NVspec_ver304e
6
Collective Alarm for Indoor Uni
network output SNVT_switch nvoAllAlarm;
This output network variable collectively outputs the presence of indoor unit errors(nvoAlarm_n).
Abnormalities will be output if the number of the indoor units in unusual is included.
Valid Ran
e
SW1-7:OFF SW1-7:ON
state value state value
normal 0 0 0 0
Error 1 0 1 100%
*The value is 0 while LM ADAPTER is initialized.
When Transmitted
This variable is transmitted promptly when the state changes.
This variable is output by the ncilnitStartTm (Initialize Start Time) at the powering of LM ADAPTER.
Update Rate
The maximum update rate is not available.
Default Service Type
Acknowledged
7
Collective Alarm for LM ADAPTE
network output SNVT_switch nvoAllAlarmLMAP;
This output network variable collectively outputs the presence of communication errors between the LM ADAPTER
and indoor unit.
If the number of the indoor units in communication is unusual, the abnormalities in communication will be output.
Valid Ran
e
SW1-7:OFF SW1-7:ON
state value state value
Normal 0 0 0 0
communication Error 1 0 1 100%
*The value is 0 while LM ADAPTER is initialized.
When Transmitted
This variable is transmitted promptly when the state changes.
This variable is output by the ncilnitStartTm (Initialize Start Time) at the powering of LM-AP.
Update Rate
The maximum update rate is not available.
Default Service Type
Acknowledged
NOTE: The communication error are caused with the power supply OFF of an outdoor unit etc.
With the power supply OFF of an indoor unit, communication does not become unusual.
LM ADAPTER state
WSN02-2124 - 33 -