Mitsubishi Electronics LMAP03U-E Air Conditioner User Manual


 
03_NVspec_ver304e
5n
Setpoint
network input SNVT_temp_p nviSetPoint_n;
This input network variable is used to change the temperature setpoint of the indoor unit.
Valid Range
HVAC Mode Range
Auto mode 19 to 28
Heat mode 17 to 28
Cool mode 19 to 30
Dry mode 19 to 30
Fan mode Not available
Unit of set temperature : 1.0
 *Be careful that the range of set temperature may differ depending on the model of the indoor and outdoor units.
Default Value
The default value is determined by the state of the air conditioner indoor unit).
This variable becomes value = 0 until the value is updated after the power supply of LM ADAPTER.
6n
Setpoint state
network output SNVT_temp_p nvoSetPoint_n;
This output network variable indicates the present temperature setpoint of the indoor unit.
Valid Range
Output range 17 to 30
Temperature unit 1.0
*The value is 0 while LM ADAPTER is initialized.
When Transmitted
This variable is transmitted promptly as the state changes.
This variable is also transmitted as the state changes by the operation from the local side such as a local
remote controller.
This variable is output by the ncilnitStartTm (Initialize Start Time) at the powering of LM ADAPTER.
Update Rate
The value defined by nciSndHrtBt_1(SendHearbeat_1) is valid.
Default Service Type
Acknowledged
WSN02-2124 - 16 -