Mitsubishi Electronics LMAP03U-E Air Conditioner User Manual


 
03_NVspec_ver304e
2-5.Mr.SLIM
Indoor[1]-[50]
Network Variables
nv1n
nviOnOff_n
SNVT_switch
nv2n
nvoOnOff_n
SNVT_ switch
nv3n
nviMode_n
SNVT_hvac_mode
nv4n
nvoMode_n
SNVT_hvac_mode
nv5n
nviSetP_n
SNVT_temp_p
nv6n
nvoSetP_n
SNVT_temp_p
nv9n
nviFanSpeed_n
SNVT_switch
nv10n
nvoFanSpeed_n
SNVT_switch
*3,4,5 nv11n
nviProOnOff_n
SNVT_switch
nv12n
nvoProOnOff_n
SNVT_switch
*3,4,5
*3,4,5 nv13n
nviProMode_n
SNVT_switch
nv14n
nvoProMode_n
SNVT_switch
*3,4,5
*3,4,5 nv15n
nviProSetP_n
SNVT_switch
nv16n
nvoProSetP_n
SNVT_switch
*3,4,5
*6 nv17n
nviThermoOff_n
SNVT_switch
nv18n
nvoThermoOff_n
SNVT_switch
*6
*7 nv19n
nviFiltReset_n
SNVT_switch
nv21n
nvoSpaceTemp_n
SNVT_temp_p
nv22n
nvoAlarm_n
SNVT_switch
nv23n
nvoErrCode_n
SNVT_count
nv24n
nvoErrAdrs_n
SNVT_count
nv25n
nvoThermoSt_n
SNVT_state
nv26n
nvoThermo_n
SNVT_switch
nv28n
nvoIcMdlSize_n
SNVT_count
nc29n
nvoGroupNo_n
SNVT_count
*8
*1: stencil for LonMaker:MrSLIM[1]-[50]
*2: "n" of the network variable shows M-NET address of Mr.SLIM.
*3: It may be unable to be used by the system configuration of air-conditioners units.
*4: It is possible to use with an "MA" remote controller.
*5: For the use of this function, turn ON the switch(SW1-1) on LM ADAPTER.(Factory setting "OFF")
*6: For the use of this function, turn ON the switch(SW1-8) on LM ADAPTER.(Factory setting "OFF")
*7: For the use of this function, turn ON the switch(SW1-4) on LM ADAPTER.(Factory setting "OFF")
*8: It is possible to use with other system controller.
WSN02-2124 - 8 -