Mitsubishi Electronics LMAP03U-E Air Conditioner User Manual


 
03_NVspec_ver304e
4.Network Variables
1n
Request On/Off
network input SNVT_switch nviOnOff_n;
This input network variable is used to run or stop the indoor unit or ventilator (during independent non-interlocked
operation).
When the ventilator (LOSSNAY) is registered as interlocking with indoor unit, it will turn the indoor unit ON (for
high speed) and OFF. Instructions according to this network variable in under nvoAllOff's output of the state of
"Emergency Off" are disregarded.
Valid Range
indoor unit interlocked ventilato
r
state value state value
0 not used
1 (*2) 0
ON(high) 0 100% (*1,3)
1
not used
else
not used
*1:The value field is set in 0% usually.
*2:The setting to state=0x02-0xFE is interpreted as state=0x01.
The setting to state=0xFF is invalid.
*3:The setting to over 100% is interpreted as 100%.
Default Value
The default value is determined by the state of the air conditioner (indoor unit).
This variable becomes value = 0 until the value is updated after the power supply of LM ADAPTER.
2n
On/Off run state
network output SNVT_switch nvoOnOff_n;
This output network variable indicates the present On/Off state of the indoor unit or ventilator.
When the ventilator (LOSSNAY) is registered interlocking with the indoor unit, the state of the ventilator will not
be output, but it will operate (On/Off) the same as the indoor unit.
Valid Range
indoor unit interlocked ventilato
r
state value state value
OFF
OFF 0 0%
ON(low) 0 50%
ON(high) 0 100%
ON
any
10
1 100%
When Transmitted
This variable is transmitted promptly as its state changes.
This variable is also transmitted as the state changes by the operation from the local side such as a local
remote controller.
This variable is output by the ncilnitStartTm (Initialize Start Time) at the powering of LM ADAPTER.
Update Rate
The value defined by nciSndHrtBt_1 (Send Heartbeat_1) and nciMinOutTm (Minimum Send Time) is valid.
Default Service Type
Acknowledged
SW1-7OFF SW1-7O
SW1-7O
0
1 (*2) 0.5% to 100% (*3)
SW1-7OFF
0% to 99.5 % (*1)
Unit State
ON
OFF
ON(high)
OFF
Unit State
00
WSN02-2124 - 14 -