Request Collective Operation Prohibit
network input SNVT_switch nviAllPro;
This input network variable is used to collectively prohibit (On/Off, operation mode, temperature setting operations)
of the local remote controller connected to the indoor unit or ventilator (during independent non-interlocked operation).
Instructions according to nviProOnOff_n,nviProMode_n,and nviProSetP_n, in under the prohibition of collective operation
(nvoAllPro outputs "Enable") are held.
The effective time is set according to nviEffectTm_2(Effective Time_2).
Valid Range
SW1-7OFF SW1-7O
state value state value
1 not used 1 (*1) 0.5% to 100% (*2)
*1:The setting to state=0x02-0xFE is interpreted as state=0x01.
The setting to state=0xFF is invalid.
*2:The setting to over 100% is interpreted as 100%.
   *This operation is not carried out when there are inputs other than the above.
    The present instruction state is continued.
Default Value
This variable become state=0 and value = 0 until the value is updated after the power supply of LM ADAPTER.
NOTE:
1
:
For the use of this function, turn ON the switch (SW1-1) on LM ADAPTER.(Factory setting "OFF")
2
:
It is possible to use with an "MA" remote controller.
5
Collective Local Prohibit state
network output SNVT_switch nvoAllPro;
This output network variable indicates the state of collective operation prohibiting.
Valid Range
SW1-7OFF SW1-7O
state value state value
disable 0 0 0 0
enable 1 0 1 100%
*The value is 0 while LM ADAPTER is initialized.
When Transmitted
This variable is transmitted promptly when the state changes.
Update Rate
The maximum update rate is not available.
Default Service Type
Acknowledged
NOTE:
1
:
For the use of this function, turn ON the switch (SW1-1) on LM ADAPTER.(Factory setting "OFF")
2
:
It is possible to use with an "MA" remote controller.
Enable
Collective Local Prohibit
Collective Operation Prohibit
WSN02-2124 - 32 -