Send Heartbeat Start Time
network input config SNVT_time_sec nciStartHrtBt
This configuration property defines the start time of automatic updating at the powering of the LM ADAPTER.
The objective configuration properties are given below.
・nciSndHrtBt
_
1(Send Heartbeat
_
1)
・nciSndHrtBt
_
2(Send Heartrbeat
_2
)
Valid Range
The valid range covers from 1200.0 to 6540.0 seconds (per 60 seconds).
The setting to 0.0 or 6553.5 seconds results in 1800.0 seconds.
The setting to 0.1 - 1199.9 seconds results in 1200.0 seconds.
The setting to 6540.1- 6553.4 seconds results in 6540.0 seconds.
Default Value
6553.5 seconds (judged as 1800 seconds)
17
Send Start Time
network input config SNVT_time_sec nciStartOutTm
This configuration property defines the start time of the output network variable change at powering of LM ADAPTER.
The objective network variables are given below.
・nvoOnOff_n(On/Off run state)
・nvoMode_n(Mode state)
・nvoSetP_n(SetPoint state)
・nvoLCMode_n(LOSSNAY Mode state)
・nvoFanSpeed_n(Fanspeed state)
・nvoProOnOff_n(Local Prohibit On/Off state)
・nvoProMode_n(Local Prohibit Mode state)
・nvoProSetP_n(Local Prohibit SetPoint state)
・nvoThermoOff_n(Forced Thermostat OFF state)
・nvoOnTime_n(Filter Run Time)
・nvoSpaceTemp_n(Space Temperature)
・nvoAlarm_n(Alarm state)
・nvoErrCode_n(Error Code)
・nvoErrAdrs_n(Error Unit Address)
・nvoThermoSt_n(Thermo On/Off state_1)
・nvoThermo_n(Thermo On/Off state_2)
・nvoAllOnOff(Collective On/Off state)
・nvoAllOff(Emergency state)
・nvoAllPro(Collective local prohibit state)
・nvoDefrost(Collective Defrosting state)
・nvoAllAlarm(Collective Alarm for Indoor Unit)
・nvoAllAlarmLMAP(Collective Alarm for LM ADAPTER)
Valid Range
The valid range covers from 1200.0 to 6540.0 seconds (per 60 seconds).
The setting to 0.0 or 6553.5 seconds results in 1800.0 seconds.
The setting to 0.1 - 1199.9 seconds results in 1200.0 seconds.
The settin
g
to 6540.1 ~ 6553.4 seconds results in 6540.0 seconds.
Output data is as follows by setup of Variable A and Variable B.
Default Value
6553.5 seconds (judged as 1800 seconds)
NOTE: Output data is as follows by setup "Initialize Start Time" and "Communication Timing".
Setting "Initialize":
An initial output value or a value at a power supply ON to the time of 20-minute progress.
Setting "setting time":
An initial output value or a value at the time of Neuron Chip communication start.
WSN02-2124 - 37 -