Honeywell 5820XL Smoke Alarm User Manual


 
IntelliKnight 5820XL Installation Manual
4-16 151209
4.6 5815XL Installation
The 5815XL SLC expander lets you add 127 addressable devices. Up to three 5815XLs
(adding 381 SLC devices for a total of 508 points) can be used with the system.
To install the 5815XL:
1. Make sure power is off at the panel.
2. Mount the 5815XL in the 5820XL, the 5895XL cabinet, or the 5815RMK remote mount-
ing kit. Use the standoffs located under the control panel board assembly and secure with
screws provided with the 5815XL. See also Model 5895XL Installation Instructions (P/N
151142) or 5815RMK Remote Mounting Kit Installation Instructions (P/N 151391).
3. Connect the 5815XL to the control panel. (See Section 4.6.1.)
4. Use on-board dipswitches to select an ID#. (See Section 4.10.1.)
5. The new 5815XL module must be added to the system through programming. JumpStart
will add the module automatically (see Section 6.1). You can also add it manually (see
Section 7.3.2). Select a name, if desired (see Section 7.3.1.1).
6. You are now ready to connect SLC devices to the 5815XL (see Section 5.4).
Figure 4-15 is a drawing of the 5815XL board, showing the location of terminals and
dipswitches.
Figure 4-15 5815XL Board