Honeywell 5820XL Smoke Alarm User Manual


 
IntelliKnight 5820XL Installation Manual
7-16 151209
Response with System-Wide Conditions
You can select whether an output group will respond to various system-wide occurrences.
(See Figure 7-8 for location of this field.)
11. To get to this menu item repeat steps 1 through 6 of Section 7.5.1.
12. To edit group properties, press .
13. Press the or arrows to select the desired latching option.
14. Press .
15. Press the or arrows to select the desired silencing option. Refer to Table 7-2.
AUT UNSIL Auto Unsilenced. If this option is selected, the output group can be silenced for a programmed time-
frame. If the condition that caused the output to activate has not cleared during the time-frame, the
output reactivates. If you select this option, select the time-frame in the DLY: field. Range is 00-60
minutes. (See Figure 7-8 for location of field.)
SIL-INHIB Timed Silence after Inhibit. If this option is selected, the output group must be audible for a
programmed number of minutes before it can be silenced. If the condition that caused the output to
activate has not cleared during the time-frame, the output can be silenced. If you select this option,
select the timeframe in the DLY: field. Range is 00-60 minutes. (See Figure 7-8 for location of field.)
SHUT-DOWN If this option is selected, the output group will automatically silence (shut down) after the
programmed time period. If you select this option, select the timeframe in the DLY: field. Range is
01-60 minutes. (See Figure 7-8 for location of field.)
Table 7-3: Output Group Response Choices
Option Description
ManPull Manual Pull Activation. Select Yes if you want this group to activate for all manual pull
alarms that occur in the system.
Note: Even though manual pull switches are assigned to zones, activation
selected here for manual pull will override zone-programmed activation.
Fire Drill Fire Drill Activation. Select Yes if you want this group to activate for fire drills.
Sys Aux1 and Sys Aux2 Select Yes if you want this output group to activate for system-wide Aux1 and Aux2
alarms.
(Aux 1 and Aux 2 alarm types are for auxiliary alarm conditions. For example, you
might want to use Aux 1 to provide a unique alarm type.)
Ignore Global Cad Ignore Global Cadence. If you want to create an output group that can never be
overridden, you can select Yes for this option. Selecting No means that system-wide
events that have been assigned an output pattern could override the pattern for the
output group.
For example, suppose you had assigned a set of strobes to Output Group 3. You would
never want these strobes to output in a pattern under any circumstances. To make sure
this happens, select Yes for Ignore Global Cadence for Output Group 3.
Reverse Polarity This option programs the output group for reverse polarity operation. Selecting Reverse
Polarity–Troubles will cause the output group to be de-energized for any system
trouble. Selecting Reverse Polarity–No Troubles will cause system troubles to be
ignored. Activation is accomplished through standard mapping methods. Use with the
7644 assembly to implement reverse polarity. See Section 4.15.3.2 for more
information on the 7644.
Table 7-2: Silencing Options
Option Description
2