Honeywell 5820XL Smoke Alarm User Manual


 
IntelliKnight 5820XL Installation Manual
7-28 151209
7.7.1 Reporting Account
Up to four reporting accounts can be used with the control panel. Events in accounts are
reported by zone.
Each account is assigned an up-to-6-digit account number. Each account is also assigned a
unique ID (1-4) which determines the priority for reporting ("1" has the highest priority; "4"
has the lowest).
Disable any unused accounts by selecting “N” for all events (see Figure 7-12). If the system is
local only (does not connect to a central station), disable all events for all four reporting
accounts.
Options for each account can be customized. These options appear on the Reporting Accounts
screen. Some related options appear on the Phone Lines screen (see Section 7.7.2).
To access the Reporting Accounts screen:
1. Enter the installer code.
2. Press or to display the main menu.
3. Select for Program Menu.
Display reads: Initializing
Please wait . . .
4. From the Program Menu, select for System Options.
5. From the next menu, select for Reporting Accounts.
7
5
0