Honeywell 5820XL Smoke Alarm User Manual


 
IntelliKnight 5820XL Installation Manual
3-14 151209
U Select alarm delay options (detection characteristics) for zone. 7.4.1.2
U Select heat detector trip temperature. (JumpStart selects 150°F for heat
detectors.)
7.4.1.2
Output Point Configuration
Conventional notification circuits (circuits 1-6):
U Enable circuits used for notification appliances through programming, if
necessary. (JumpStart enables circuits 1-6 as Notification.)
7.5.1
Conventional relay circuits (circuits 7-8):
U Select options for relay circuits, if desired. Note: Relay circuits will always
output continuously (constant pattern), even if assigned to an Output Group
that uses a different output pattern.
7.5.1
Auxiliary power circuits (circuits 1-6):
U Enable any circuit used for auxiliary power devices through programming. 7.6
U Select type of power (door holder, constant, or resettable) 7.6
Addressable relay modules
U Assign addressable relay modules to output groups through programming.
(JumpStart assigns all relay modules to Group 1.)
7.6
LED output points (from the 5880 LED I/O module or 5865/66 LED Annunciator)
U Assign LED modules to output groups through programming. 7.6.3
All output circuits (1-8):
U Disable (set to UNUSED) any unused circuits. If you do not disable unused
output circuits, they will cause a trouble condition (unless an EOL resistor
is used).
7.6
U Select a name for the point, if desired. 7.6
Output Group Configuration
U Add the group to the system if it does not already exist. 7.5.2
U Assign output points to the group. 7.6
U Program a name (or description) for the group, if desired. 7.5.1.1
Select “group properties” (see below).
U Latching / non-latching 7.5.1
U Silencing option 7.5.1
U Select options for activation with system switches. 7.5.1
U Map zones to output groups that will activate when zone goes into alarm. 7.4.1.3
U Select a cadence pattern for outputs in the zone. 7.4.1.3
Task
See Sec.
(for more info.)