Honeywell 5820XL Smoke Alarm User Manual


 
Programming
151209 7-15
8. Select the characters for the zone name by pressing the or arrow until the desired
character is shown then press .
OR
Enter the Numerical Designator for the character you want, then press . See Appendix B
of this manual for a list of available characters and their numeric designators.
9. Repeat step 8 until the name is complete.
10. Press when the name is complete.
7.5.1.2 Edit Group Properties
The Edit Group Menu allows you to select options for each group for the following items:
Latching or non-latching outputs.
Silencing operation.
Operation with system switches.
Figure 7-8 Group Properties Screen Programming Options
Latching / Non-latching Outputs
Outputs that are programmed as Latching remain active until the system has been manually
reset. Non-latching outputs stop activating automatically when the condition clears.
Silencing Options
The following silencing options are available for each output group.
Table 7-2: Silencing Options
Option Description
SILENCE
Silenceable. The output group can be silenced through the key.
NON-SIL
Not silenceable. The output group cannot be silenced. Activation of the key will be
ignored for this output group.
SILENCE