Honeywell 5820XL Smoke Alarm User Manual


 
IntelliKnight 5820XL Installation Manual
7-30 151209
Events to Report
The next six options select which types of events (or event families) will be reported to this
account. (See Figure 7-12 for location of these options on the screen.) Events are reported by
zone.
10. Press the or arrow to select Must, Yes, or No (see table below), then press .
11. Repeat step 10 for all six event report options.
For each event family, select M, Y, or N.
Switch Attempts
Specify the number of times the dialer should attempt to report to this account before
switching to the next account. Range is 01-15.
12. Enter the number of switch attempts (or press the or arrow), then press .
Fail Attempts
This feature specifies the number of times the dialer should attempt to perform the dial/switch
sequence before issuing an account trouble condition. Range is 01 - 15 (Default = 10).
13. Enter the number of fail attempts (or press the or arrow), then press .
Selecting Primary and Secondary Phone Lines
For each account, select which phone line (Line 1 or Line 2) is primary. See Figure 7-12 for an
example of how to make this selection.
14. Press the or arrow to select line 1 or 2 as primary phone line, then press .
Event Family Events Included in this Family
Alarms All alarms (Water Flow, Manual Pull, Detectors, Auxiliary Switches)
Alarm Restore All alarm restores.
Supervisory/Trouble All trouble and supervisory conditions and trouble and supervisory restores.
Enable/Disable Point Enabling and disabling of input and output points.
Service/Test Fire drill, walk test, dialer test, automatic test, all programming sessions.
System Reset All system resets.
M(ust) Must Report. Selecting "M" makes this a primary reporting account for this family of events. The dialer
MUST report events in this family to this account.
Selecting Must makes an account a primary reporting account. The dialer will try to report the event to
the primary account until it exceeds the "Switch Attempts" value. When the dialer has exceeded the
Switch Attempt retry limit, it will switch to a backup account (a "Can Report" or "Yes" account, see
below). If the dialer cannot report the event to any of the backup accounts, it will return to the primary
account and repeat the process until it exceeds the "Fail Attempts" value. If the Fail Attempts limit is
exceeded, an Account Trouble condition is generated and a local trouble will sound.
Y(es) Can Report. Selecting Y makes this a backup account for this event family. The dialer will report to this
account only if it was previously unable to report the event to a Must account.
N(o) No events in this family will ever be reported to this account.