8.7.1 Single Interlock Zone Releasing
A single interlock zone utilizes a minimum of two addressable detectors and a designated
manual release switch.
Conditions Required for an Pre-Alert Output Activation
If any single addressable detector is activated, the “Pre-Alert” output will activate. This alerts
the user that the initial stages required for a release condition are present. (Also refer to Table
8-3.)
Conditions required for an General Alarm and Release Output Activation
If two or more addressable detectors, or a manual release switch activate, the “Alarm” and the
“Release” outputs will activate. (Also refer to Table 8-3.)
Important!
Only addressable detectors can be used. No conventional detectors can be used.
Each Single Interlock Zone input requires at least one manual release switch.
Table 8-3: Single Interlock Zone Operation
Inputs Output Results
1st Addressable Detector
2nd Addressable Detector
Manual Release Station
Normal
Pre-Alert
Pre-Alert
Release and General Alarm
Release and General Alarm
Release and General Alarm
Release and General Alarm
Release and General Alarm