Honeywell 5820XL Smoke Alarm User Manual


 
Programming
151209 7-29
7.7.1.1 Edit Accounts
6. From the next menu, select for Edit Account.
A screen similar to one shown in Figure 7-12 will display. The following subsections
describe the options on each field.
Figure 7-12 Reporting Account Editing Screen
Select Account (ID)
The control panel provides up to 4 reporting accounts. The priority of an account is based on
its account ID. Account 1 is highest priority; Account 4 is lowest. Use Account 1 to report the
highest priority events.
7. Press the or arrow to select account ID number, then press .
Edit Account Number
Enter an up-to-6-digit number for each account to identify the account to the central station.
See Figure 7-12 for location of this option on the screen. The account number should be
compatible with the reporting format used. For example, the Contact ID format transmits up
to four digits only.
8. Enter the desired account number (up to 6-digits), then press .
Select Reporting Format
Select a reporting format for each account. Options are:
9. Press the or arrow to select the reporting format, then press .
SIA SIA format. 8 events per call.
CID Ademco’s Contact ID format
S20 Same as SIA but limits events reported to 20 events per phone call.
1