Honeywell 5820XL Smoke Alarm User Manual


 
IntelliKnight 5820XL Installation Manual
3-2 151209
3.3 Electrical Specifications
Terminal # and Label Description
Rating
Earth Ground
Faults
Voltage Current
1 L AC input (hot) 120 VAC, 60 Hz 2.5 A N/A
2 Earth ground N/A N/A N/A
3 N AC input (neutral) 120 VAC 60 Hz 2.5 A N/A
4X
*I/O 6 Flexput™ Circuits 24 VDC
3.0 Amp Notification and
Aux power Circuits
0Ω
5 O 100 mA for initiation circuits
6 X
*I/O 5 Flexput™ Circuits 24 VDC
3.0 Amp Notification and
Aux power Circuits
0Ω
7 O 100 mA for initiation circuits
8X
*I/O 4 Flexput™ Circuits 24 VDC
3.0 Amp Notification and
Aux power Circuits
0Ω
9 O 100 mA for initiation circuits
10 X
*I/O 3 Flexput™ Circuits 24 VDC
3.0 Amp Notification and
Aux power Circuits
0Ω
11 O 100 mA for initiation circuits
12 X
*I/O 2 Flexput™ Circuits 24 VDC
3.0 Amp Notification and
Aux power Circuits
0Ω
13 O 100 mA for initiation circuits
14 X
*I/O 1 Flexput™ Circuits 24 VDC
3.0 Amp Notification and
Aux power Circuits
0Ω
15 O 100 mA for initiation circuits
16 B
SBUS OUT
SBUS communication 5 VDC 100 mA
0Ω
17 A
18 +
SBUS power 24 VDC 1.0 A
19 -
20 B
SBUS IN Used for Class A installations 0Ω
21 A
22 +
23 -
24 N.C.
RELAY 2 General Purpose Relay 2 24 VDC 2.5 A, resistive N/A25 C
26 N.O.
27 N.C.
RELAY 1 General Purpose Relay 1 24 VDC 2.5 A, resistive N/A28 C
29 N.O.
30 N.C.
TROUBLE Trouble Relay 24 VDC 2.5 A, resistive N/A31 C
32 N.O.
33 SC- L1
SLC OUT
SLC terminals 32 VDC 150 mA 0Ω
34 SC+
35 SC- L2
SLC IN
Used for Class A installations 0Ω
36 SC+
* Regulated/Special application when used for releasing.