SLC Device Hardware Installation
Perform these steps before running JumpStart.
U Connect device bases to the loop. SK 5.5
Hochiki 5.3
U Set device addresses. SK 5.6
Hochiki 5.8
U Physically connect detectors to their bases. Connect relay and contact
monitor modules.
5.4 & see device
install instructions
JumpStart
JumpStart is for initial system programming. JumpStart automatically selects
some options for SLC devices. See “Input Point Configuration” section of this
chart for other options.
JumpStart makes selections for the following options. You can customize
options, if necessary.
6.1 & 7.8
Device type (detector or switch) configured by JumpStart. To change, see 7.6
Program type of detector (heat, photoelectric, or ionization) selected by
JumpStart.
To change, see 7.6
System Software Configuration
U Select low AC hours report time (6 hours by default). 7.7.4.2
U Select Auto Test Time (2:00 AM by default). 7.7.1.2
U Enable/disable automatic DST adjustment feature (enabled by default). 7.7.4.3
U Change clock display format (12-hour with AM/PM by default). 7.7.4.4
U Set up reporting accounts. 7.7.1
U Select options for phone lines. 7.7.2
U Select system-wide response to trouble conditions, if desired. 7.7.3
U Select system-wide cadence patterns for special conditions (fire drill, Aux1
and Aux2 alarms) if desired.
7.7.3
U Customize banner message (message that displays on LCD in normal
mode) if desired.
7.7.7
Input Point (SLC Device) Configuration
JumpStart automatically selects some options for SLC devices (see “JumpStart” section of this chart).
You can change options selected by JumpStart, if necessary and further customize input point options.
U Select device type (SK or Hochiki). Only one device type can be used per
control panel.
7.2
U Program type of switch (manual pull, fire drill, and so on), if necessary.
(JumpStart assigns all switches as Manual Pull type.)
7.6
U If the installation includes duct detectors, program detector type.
(JumpStart does not distinguish duct detectors from ordinary smoke
detectors.)
7.6
U Assign a name (or description) to the point. 7.6.3.1
U Assign input points to zones, if necessary. (JumpStart assigns all input
points to Zone 1.)
7.6
Zone Configuration
U Add the zone to the system if it does not already exist. (Zone 1 created by
JumpStart.)
7.4.2
U Program a name (or description) for the zone. 7.4.1.1
Task
See Sec.
(for more info.)