Honeywell 5820XL Smoke Alarm User Manual


 
IntelliKnight 5820XL Installation Manual
7-18 151209
7.5.4 View Group Points
1. Enter the installer code.
2. Press or to display the main menu.
3. Select for Program Menu.
Display reads: Initializing
Please wait . . .
4. Press to enter group menu.
5. Press to view group points.
6. Enter the group number, then press .
7.5.5 Edit Output Group Templates
Some installations may require that zones be mapped to more than 8 output groups. With
output group templates you can combine one or all output groups into one template, which can
be used when the same combination of outputs are used for several zones.
For example, lets say an installation has five zones (See Table 7-4). The check mark indicates
what output groups are mapped to each zone. You will notice that every zone is mapped to
outputs 1 and 2. As an alternative you can create a template that combines output group 1 and
2 as one choice.
This can be done by creating a template which includes output groups 1 and 2. Then you can
map all the zones to the template you created. This will free up output group assignments that
are common to several zones. This is very useful when you need to map zones to more than
Table 7-4: Zone Group Example
Zone
Group Number
12345678
1st Floor Smoke Detectors 
2nd Floor Smoke Detectors 
3rd Floor smoke Detectors 
Manual Fire Pull Stations 
Water Flow Switches 
7
3
4