Carrier 42V Air Conditioner User Manual


 
8
LEGEND
1— Junction Box, Installed with Plenum
2— Flexible Metal Conduit
3— Insulated Plenum
4— Mounting Bracket
5— Drain Conn,
7
/
8
-in. OD
6— Tell-Tale Drain Conn,
5
/
8
-in. OD (optional)
7— Drip Lip (optional, shipped loose)
8— Filter
9— Return Duct Collar, 1-in.
10 — Access Panel
11 — Supply Duct Collar, 1-in.
12 — Supply Conn,
5
/
8
-in. OD
13 — Air Vent,
1
/
8
-in. MPT
14 — Return Conn,
5
/
8
-in. OD
15 — Hanger Slots (4), Rubber Grommet has
3
/
8
-in. Diameter Hole
*Unit weights are based on dry coils and minimum rows. Weights exclude packaging, valves, and other components.
UNIT
SIZE
NOM
AIRFLOW
(Cfm)
DIMENSIONS (in.) QTY/UNIT FACE
AREA
(sq ft)
UNIT
WEIGHT*
(lb)
AA’BCD’E F GH
Blower Motor
04 400 31
1
/
4
43
1
/
4
26 28
1
/
4
15 29
3
/
4
6
1
/
4
8
3
/
4
30
1
/
4
2 1 1.35 84
06 600 36
1
/
4
43
1
/
4
34 33
1
/
4
10 34
3
/
4
7
1
/
2
10 35
1
/
4
2 1 1.88 97
08 800 43
1
/
4
57
1
/
4
38 40
1
/
4
17 41
3
/
4
7
1
/
2
10 42
1
/
4
2 1 2.31 110
10 1000 57
1
/
4
65
1
/
4
52 54
1
/
4
11 55
3
/
4
7
1
/
2
10 56
1
/
4
4 2 3.16 163
NOTES:
1. Right hand unit shown; left hand unit opposite. Coil connection
locations are ±
5
/
8
-in.
2. Unit sizes 04 thru 08 have one motor, 2 blowers; size 10 has
2 motors, 4 blowers.
3. Refer to above figure for configuration of filter and track if
installed in optional plenum.
4. Dimension increases by 4 in. with optional electric heat.
5. Not shown: 3-speed fan switch; wall plate,
1
/
2
-in. fiberglass
insulation on inside of plenum (when installed), closed cell
insulation on main drain pan.
6. Units have galvanized finish.
7. For optional coil connections, view 42CA-203-1 using the Fan
Coil Builder.
8. Dimensions shown in inches (mm).
A42-4103
Fig. 5 — 42CF Furred-In High-Static Horizontal Unit with Plenum Dimensions