69
Table 7 — 30XA140-500 Electrical Data, Single Point (High Ambient Option)
LEGEND
NOTES:
1. Units are suitable for use on electrical systems where voltage supplied to the unit ter-
minals is not below or above the listed minimum and maximum limits. Maximum allow-
able phase imbalance is: voltage, 2%; amps 10%.
2. Cooler heater is wired into the control circuit so it is always operable as long as the
control power supply disconnect is on, even if any safety device is open.
3. For MCA that is less than or equal to 380 amps, 3 conductors are required.
For MCA between 381-760 amps, 6 conductors are required.
For MCA between 761-1140 amps, 9 conductors are required.
For MCA between 1141-1520 amps, 12 conductors are required.
Calculation of conductors required is based on 75 C copper wire.
4. Wiring for main field supply must be rated 75 C minimum. Use copper for all units.
a. Incoming wire size range for the terminal block is no. 4 AWG (American Wire Gage)
to 500 kcmil.
b. Incoming wire size range of non-fused disconnect with MCA up to 599.9 amps is
3/0 to 500 kcmil.
c. Incoming wire size range of non-fused disconnect with MCA from 600 to 799.9 amps
is 1/0 to 500 kcmil.
d. Incoming wire size range of non-fused disconnect with MCA from 800 to 1199.9 amps
is 250 kcmil to 500 kcmil.
5. Data provided circuit 1/circuit 2 where there are two circuits.
UNIT
30XA
UNIT VOLTAGE
NUMBER
OF
COND
FANS
NO HYDRONIC PACKAGE 5 HP PUMP, 3450 RPM 7.5 HP PUMP, 3450 RPM CONTROL CIRCUIT
V-Hz
(3 Ph)
Supplied
MCA MOCP
ICF Rec
Fuse
Size
MCA MOCP
ICF Rec
Fuse
Size
MCA MOCP
ICF Rec
Fuse
Size
Voltage
1 PH,
60 Hz
MCA
and
MOCP
Min Max WD XL WD XL WD XL
140
230-60 207 253 10 562.0 800 838.9 — 700 578.0 800 854.9 — 700 585.2 800 862.1 — 700 115 40
200-60 187 220 10 618.8800 952.8 — 700 636.5 800 970.5 — 800 644.4 800 978.5 — 800 115 40
460-60 414 506 10 281.0 400 419.5 1051.5 350 289.0 400 427.5 1059.5 350 292.6 400 431.1 1063.1 350 115 40
575-60 518 633 10 216.3 300 332.5 838.5 250 222.7 300 338.9 844.9 250 225.6 300 341.8847.8 250 115 40
380-60 342 418 10 328.3 450 504.6 1269.6 400 338.0 450 514.3 1279.3 400 342.3 450 518.7 1283.7 400 115 40
160
230-60 207 253 10 642.7 800 1036.7 — 800 658.7 800 1052.7 — 800 665.9 800 1059.9 — 800 115 40
200-60 187 220 10 706.9 1000 1179.4 — 800 724.5 1000 1197.1 — 1000 732.5 1000 1205.0 — 1000 115 40
460-60 414 506 10 320.5 450 518.0 1326.0 400 328.5 450 526.0 1334.0 400 332.1 450 529.6 1337.6 400 115 40
575-60 518 633 10 247.2 350 412.1 1058.1 300 253.6 350 418.5 1064.5 300 256.5 350 421.4 1067.4 300 115 40
380-60 342 418 10 374.9 500 622.8 1601.8 450 384.6 500 632.5 1611.5 450 388.9 500 636.8 1615.8 450 115 40
180
230-60 207 253 12 703.9 800 980.8 — 800 — — — — — — — — — — 115 40
200-60 187 220 12 775.0 1000 1109.1 — 1000 — — — — — — — — — — 115 40
460-60 414 506 12 351.9 450 490.4 1122.4 400 — — — — — — — — — — 115 40
575-60 518 633 12 271.1 350 387.3 893.3 300 — — — — — — — — — — 115 40
380-60 342 418 12 410.8 500 587.2 1352.2 450 — — — — — — — — — — 115 40
200
230-60 207 253 12 795.6 1000 1189.6 — 1000 — — — — — — — — — — 115 40
200-60 187 220 12 875.0 1200 1347.5 — 1000 — — — — — — — — — — 115 40
460-60 414 506 12 396.9 500 594.4 1402.4 450 — — — — — — — — — — 115 40
575-60 518 633 12 305.8 400 470.7 1116.7 350 — — — — — — — — — — 115 40
380-60 342 418 12 463.8 600 711.7 1690.7 600 — — — — — — — — — — 115 40
220
230-60 207 253 13 876.7 1200 1200.4 — 1000 — — — — — — — — — — 115 40
200-60 187 220 13 964.6 1200 1359.4 — 1200 — — — — — — — — — — 115 40
460-60 414 506 13 438.0 600 599.8 1407.8 500 — — — — — — — — — — 115 40
575-60 518 633 13 337.6 450 475.0 1121.0 400 — — — — — — — — — — 115 40
380-60 342 418 13 511.5 700 718.3 1697.3 600 — — — — — — — — — — 115 40
240
230-60 207 253 13 933.0 1200 1256.7 — 1200 — — — — — — — — — — 115 40
200-60 187 220 13 1026.7 1200 1421.6 — 1200 — — — — — — — — — — 115 40
460-60 414 506 13 466.5 600 628.3 1436.3 600 — — — — — — — — — — 115 40
575-60 518 633 13 359.5 450 497.0 1143.0 400 — — — — — — — — — — 115 40
380-60 342 418 13 544.4 700 751.2 1730.2 600 — — — — — — — — — — 115 40
260
460-60 414 506 15 529.1 700 806.6 2028.6 600 — — — — — — — — — — 115 40
575-60 518 633 15 407.4 500 639.7 1617.7 500 — — — — — — — — — — 115 40
380-60 342 418 15 616.7 800 969.3 2448.3 700 — — — — — — — — — — 115 40
280
460-60 414 506 16 563.0 800 840.5 2062.5 700 — — — — — — — — — — 115 40
575-60 518 633 16 433.6 600 665.9 1643.9 500 — — — — — — — — — — 115 40
380-60 342 418 16 656.2 800 1008.8 2487.8800 — — — — — — — — — — 115 40
300
460-60 414 506 16 619.6 800 840.5 2062.5 700 — — — — — — — — — — 115 40
575-60 518 633 16 476.7 600 665.9 1643.9 600 — — — — — — — — — — 115 40
380-60 342 418 16 722.3 1000 1008.8 2487.8 1000 — — — — — — — — — — 115 40
325
460-60 414 506 18 638.1 800 915.6 2137.6 700 — — — — — — — — — — 115 40
575-60 518 633 18 491.2 600 723.5 1701.5 600 — — — — — — — — — — 115 40
380-60 342 418 18 743.0 1000 1095.6 2574.6 1000 — — — — — — — — — — 115 40
350
460-60 414 506 18 694.6 800 915.6 2137.6 800 — — — — — — — — — — 115 40
575-60 518 633 18 534.2 700 723.5 1701.5 600 — — — — — — — — — — 115 40
380-60 342 418 18809.1 1000 1095.6 2574.6 1000 — — — — — — — — — — 115 40
400
460-60 414 506 20 760.8 1000 1038.3 2260.3 1000 — — — — — — — — — — 115 50
575-60 518 633 20 585.7 700 818.1 1796.1 700 — — — — — — — — — — 115 50
380-60 342 418 20 886.5 1000 1239.1 2718.1 1000 — — — — — — — — — — 115 50
450
460-60 414 506 22 889.1 1000 1110.0 2332.0 1000 — — — — — — — — — — 115 50
575-60 518 633 22 683.4 800 872.7 1850.7 800 — — — — — — — — — — 115 50
380-60 342 418 22 1035.9 1200 1322.4 2801.4 1200 — — — — — — — — — — 115 50
500
460-60 414 506 22 937.6 1200 1158.5 2380.5 1200 — — — — — — — — — — 115 50
575-60 518 633 22 720.8800 910.0 1888.0 800 — — — — — — — — — — 115 50
380-60 342 418 22 1092.4 1200 1378.8 2857.8 1200 — — — — — — — — — — 115 50
ICF — Instantaneous Current Flow
MCA — Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
WD — Wye-Delta
XL — Across-the-Line